Capacity & Density Envelope Study — Reference Colocation Campus, hall DH-02

Reference Project (synthetic) · target platform NVIDIA GB300 NVL72 · 5 architectures compared · GridForge-AI envelope engine v0.1

Site
Reference Colocation Campus
Hall
DH-02 · built 2015
Metro
Frankfurt, DE
Target platform
NVIDIA GB300 NVL72
Architectures compared
5
Basis
Screening · AACE Class 5
SYNTHETIC REFERENCE DATA — NOT A CUSTOMER ASSET. All values are modelled or assumed; none is a measurement of a real site.

1. The answer

Deployable NVIDIA GB300 NVL72 racks today, before any investment
0 racks (E0)
Limited by: platform needs 205 [174–236] A (E0) per rack; installed tap-offs rated 63 A (E5)

The binding constraint as found is rack feed / tap-off rating (electrical). platform needs 205 [174–236] A (E0) per rack; installed tap-offs rated 63 A (E5).

Deployable racks after the full headroom ladder
62 racks (E0)
Limited by: Firm supply (grid import + behind-the-meter) becomes binding
IT load unlocked
8,370 [8,180–8,800] kW (E0)
Limited by: at the recommended architecture
Time to full capacity
160 [80–210] weeks (E0)
Limited by: set by transformer capacity; reliefs assumed to run in parallel; the range is that item's own lead-time range
Indicative capex to reach it
18,800,000 [9,420,000–37,700,000] EUR (E0)
Limited by: Class 5 (order of magnitude): -50% / +100% · LOWER BOUND, not an estimate: a cost it needs has no price
These economics are not decision-grade. The capex total is a LOWER BOUND: no price exists for CDU commissioning and flushing (7 x unit, needed in 5 places); CDU hydraulic integration and controls (7 x unit, needed in 5 places). 8 of 8 priced lines are library placeholders, not prices. The grid electricity price is a placeholder (140 EUR/MWh), not the site's tariff. Installed behind-the-meter generation has no usable operating cost: BESS-2MW-8MWh: annual_run_hours not declared; BESS-2MW-8MWh: no energy cost basis (declare opex_eur_per_MWh, or fuel_price_eur_per_MWh with electrical_efficiency); BESS-2MW-8MWh: variable_om_eur_per_MWh not declared (0 if the fuel route already includes it); BESS-2MW-8MWh: fixed_om_eur_per_kW_year not declared (0 if carried elsewhere). The energy cost prices all energy at the grid tariff. Section 9 lists every component and what it rests on.
Recommended architecture: Full DLC plus behind-the-meter supply. The same hall with on-site firm supply where the grid connection binds. The only scenario whose capacity is set by what can be built rather than by the queue.

Selection objective: Maximum deployable compute. On an AI site the revenue attached to a rack dominates the capital cost of enabling it, so capacity is ranked first and capex is the tie-break. Section 9 shows every architecture against all three objectives so the ranking can be overruled with the evidence in view.

Dominant sensitivity: contracted power 20% lower takes the answer from 62 to 48 racks (section 10).
As found, this hall cannot host a single rack of the target platform. The value of this study is the ordered, costed list of what has to change — and the option to stop, which is a legitimate outcome.

2. Headroom ladder

Each row is the constraint that binds at that point, what it costs to move it, and how long that takes. Reliefs are assumed to run in parallel, so the schedule is governed by the longest lead time rather than the sum.

#ConstraintDomainRacks beforeRacks afterReliefCapexWhat it buys and how it is pricedLead timeEUR per kW unlocked
1Rack feed / tap-off ratingelectrical0 racks (E0)0 racks (E0)Higher-rated tap-off units (and busway if ampacity does not allow) — adds no racks on its own: another constraint limits the hall to the same figure, so this relieves one of several tied constraints372,000 [186,000–744,000] EUR (E0)unit price x racks fitted out · library placeholder (not a price)24 [12–40] weeks (E0)—
2Residual air load removal per rackthermal0 racks (E0)0 racks (E0)Add in-row cooling or rear-door heat exchangers for the residual air load — adds no racks on its own: another constraint limits the hall to the same figure, so this relieves one of several tied constraints558,000 [279,000–1,120,000] EUR (E0)unit price x racks fitted out · library placeholder (not a price)20 [12–32] weeks (E0)—
3Achievable facility water temperaturethermal0 racks (E0)8 racks (E0)Adiabatic assist plus trim chiller on the high-temperature loop350,000 [175,000–700,000] EUR (E0)fixed lump, not scaled to size · library placeholder (not a price) · One lump placeholder per hall. The trim chiller is sized to the liquid loop, but no loop capacity is modelled, so the lump is not scaled with hall size.32 [20–48] weeks (E0)324 EUR/kW (E0)
4Transformer capacityelectrical8 racks (E0)8 racks (E0)Replace / add transformer capacity (uprate ~60%) — adds no racks on its own: another constraint limits the hall to the same figure, so this relieves one of several tied constraints1,200,000 [600,000–2,400,000] EUR (E0)9 MVA added · unit price x quantity added · library placeholder (not a price)160 [80–210] weeks (E0)—
5UPS capacity (protected load)electrical8 racks (E0)12 racks (E0)Add UPS modules / new UPS block768,000 [384,000–1,540,000] EUR (E0)2,400 kW added · unit price x quantity added · library placeholder (not a price)30 [20–52] weeks (E0)1,420 EUR/kW (E0)
6Busway ampacityelectrical12 racks (E0)22 racks (E0)Replace busway with 800-1000 A and new tap-off units450,000 [225,000–900,000] EUR (E0)8 busway run(s) added · unit price x quantity added · library placeholder (not a price)36 [24–52] weeks (E0)333 EUR/kW (E0)
7CDU capacity (derated to site water temperature)thermal22 racks (E0)25 racks (E0)Add CDU capacity (one further unit per bank)180,000 [90,000–360,000] EUR (E0)1 CDU unit(s) added · unit price x quantity added · library placeholder (not a price) · NOT PRICED: CDU hydraulic integration and controls; CDU commissioning and flushing26 [16–40] weeks (E0)444 EUR/kW (E0)
8UPS capacity (protected load)electrical25 racks (E0)28 racks (E0)Add UPS modules / new UPS block768,000 [384,000–1,540,000] EUR (E0)2,400 kW added · unit price x quantity added · library placeholder (not a price)30 [20–52] weeks (E0)1,900 EUR/kW (E0)
9Firm supply (grid import + behind-the-meter)electrical28 racks (E0)31 racks (E0)Behind-the-meter supply: BESS-2MW-8MWh (bess, 2 MW)1,800,000 [1,260,000–2,340,000] EUR (E0)the client's own declared figure30 [19.5–40.5] weeks (E0)4,440 EUR/kW (E0)
10Busway ampacityelectrical31 racks (E0)33 racks (E0)Add two further busway runs (needs riser and routing space)112,000 [56,200–225,000] EUR (E0)2 busway run(s) added · unit price x quantity added · library placeholder (not a price)36 [24–52] weeks (E0)417 EUR/kW (E0)
11CDU capacity (derated to site water temperature)thermal33 racks (E0)34 racks (E0)Add CDU capacity (one further unit per bank)180,000 [90,000–360,000] EUR (E0)1 CDU unit(s) added · unit price x quantity added · library placeholder (not a price) · NOT PRICED: CDU hydraulic integration and controls; CDU commissioning and flushing26 [16–40] weeks (E0)1,330 EUR/kW (E0)
12Firm supply (grid import + behind-the-meter)electrical34 racks (E0)39 racks (E0)Behind-the-meter supply: GEN-5MW (gas_engine, 5 MW)4,000,000 [2,800,000–5,200,000] EUR (E0)the client's own declared figure44 [28.6–59.4] weeks (E0)5,930 EUR/kW (E0)
13Busway ampacityelectrical39 racks (E0)40 racks (E0)Add two further busway runs (needs riser and routing space)112,000 [56,200–225,000] EUR (E0)2 busway run(s) added · unit price x quantity added · library placeholder (not a price)36 [24–52] weeks (E0)833 EUR/kW (E0)
14Transformer capacityelectrical40 racks (E0)43 racks (E0)Replace / add transformer capacity (uprate ~60%)1,920,000 [960,000–3,840,000] EUR (E0)14.4 MVA added · unit price x quantity added · library placeholder (not a price)160 [80–210] weeks (E0)4,740 EUR/kW (E0)
15UPS capacity (protected load)electrical43 racks (E0)44 racks (E0)Add UPS modules / new UPS block768,000 [384,000–1,540,000] EUR (E0)2,400 kW added · unit price x quantity added · library placeholder (not a price)30 [20–52] weeks (E0)5,690 EUR/kW (E0)
16CDU capacity (derated to site water temperature)thermal44 racks (E0)47 racks (E0)Add CDU capacity (one further unit per bank)180,000 [90,000–360,000] EUR (E0)1 CDU unit(s) added · unit price x quantity added · library placeholder (not a price) · NOT PRICED: CDU hydraulic integration and controls; CDU commissioning and flushing26 [16–40] weeks (E0)444 EUR/kW (E0)
17Busway ampacityelectrical47 racks (E0)55 racks (E0)Add two further busway runs (needs riser and routing space)112,000 [56,200–225,000] EUR (E0)2 busway run(s) added · unit price x quantity added · library placeholder (not a price)36 [24–52] weeks (E0)104 EUR/kW (E0)
18Busway ampacityelectrical55 racks (E0)55 racks (E0)Add two further busway runs (needs riser and routing space) — adds no racks on its own: another constraint limits the hall to the same figure, so this relieves one of several tied constraints112,000 [56,200–225,000] EUR (E0)2 busway run(s) added · unit price x quantity added · library placeholder (not a price)36 [24–52] weeks (E0)—
19CDU capacity (derated to site water temperature)thermal55 racks (E0)61 racks (E0)Add CDU capacity (one further unit per bank)180,000 [90,000–360,000] EUR (E0)1 CDU unit(s) added · unit price x quantity added · library placeholder (not a price) · NOT PRICED: CDU hydraulic integration and controls; CDU commissioning and flushing26 [16–40] weeks (E0)222 EUR/kW (E0)
20UPS capacity (protected load)electrical61 racks (E0)62 racks (E0)Add UPS modules / new UPS block768,000 [384,000–1,540,000] EUR (E0)2,400 kW added · unit price x quantity added · library placeholder (not a price)30 [20–52] weeks (E0)5,690 EUR/kW (E0)
21Firm supply (grid import + behind-the-meter)electrical62 racks (E0)62 racks (E0)Grid reinforcement / new connection capacity from the DSO — NOT TAKEN: this relief cannot be obtained inside the model's horizon—this relief cannot be obtained inside the model's horizon260 [150–520] weeks (E0)—

Headroom ladder for the recommended architecture. A step's price follows what it adds (units, MVA, kW, racks) where the library is priced per unit; a fixed lump is marked as not scaled. A component with no price is named, never counted as zero.

Steps marked NOT TAKEN are shown because they are the next thing that binds, not because they are recommended. Their cost is excluded from the totals below.

Rungs 1, 2, 4, 18 are charged but add no racks on their own. Each relieves one of several constraints that limit the hall to the same figure at that point; without it a later rung cannot deliver its gain. They are kept, and costed, because dropping any one of them lowers the final answer — that is checked, not assumed. The EUR-per-kW column is left blank for them for the same reason: no racks are unlocked at that step.

Cumulative relief capex
14,900,000 [7,450,000–29,800,000] EUR (E0)
Limited by: Class 5 (order of magnitude): -50% / +100%
Critical-path lead time
160 [80–210] weeks (E0)
Limited by: Lead time, not construction, is usually the schedule driver.

3. Time to power

Capacity without a date is not a decision. Each relief on the ladder carries a lead time; reliefs are assumed to run in parallel, so the racks unlocked by the first N steps become available at the longest lead time among those N. One item sets the date, and it is almost never the construction work.

ElapsedRacks energisedUnlocked byDomain
32 [20–48] weeks (E0)8 racks (E0)Achievable facility water temperaturethermal
160 [80–210] weeks (E0)12 racks (E0)UPS capacity (protected load)electrical
160 [80–210] weeks (E0)22 racks (E0)Busway ampacityelectrical
160 [80–210] weeks (E0)25 racks (E0)CDU capacity (derated to site water temperature)thermal
160 [80–210] weeks (E0)28 racks (E0)UPS capacity (protected load)electrical
160 [80–210] weeks (E0)31 racks (E0)Firm supply (grid import + behind-the-meter)electrical
160 [80–210] weeks (E0)33 racks (E0)Busway ampacityelectrical
160 [80–210] weeks (E0)34 racks (E0)CDU capacity (derated to site water temperature)thermal
160 [80–210] weeks (E0)39 racks (E0)Firm supply (grid import + behind-the-meter)electrical
160 [80–210] weeks (E0)40 racks (E0)Busway ampacityelectrical
160 [80–210] weeks (E0)43 racks (E0)Transformer capacityelectrical
160 [80–210] weeks (E0)44 racks (E0)UPS capacity (protected load)electrical
160 [80–210] weeks (E0)47 racks (E0)CDU capacity (derated to site water temperature)thermal
160 [80–210] weeks (E0)55 racks (E0)Busway ampacityelectrical
160 [80–210] weeks (E0)61 racks (E0)CDU capacity (derated to site water temperature)thermal
160 [80–210] weeks (E0)62 racks (E0)UPS capacity (protected load)electrical

Energisation curve for the recommended architecture.

The date is set by transformer capacity. Every week of that lead time is a week of the site's contracted power earning nothing, so it is the first thing to attack — before any further engineering optimisation.
ScenarioRacksTime to full capacityItem that sets the date
Retained air, grid only0 racks (E0)——
Rear-door heat exchangers, grid only0 racks (E0)——
Hybrid DLC on retained plant, grid only26 racks (E0)160 [80–210] weeks (E0)Transformer capacity
Full DLC, grid only28 racks (E0)160 [80–210] weeks (E0)Transformer capacity
Full DLC plus behind-the-meter supply62 racks (E0)160 [80–210] weeks (E0)Transformer capacity

Time to power across the architectures compared.

4. Site and baseline

ItemValue
SiteReference Colocation Campus
MetroFrankfurt
CountryDE
HallDH-02
Built2015
Floorraised floor
Containmentcold aisle
Rack positions560 positions (E3)
Positions available180 positions (E3)
Design density8 kW (E5)
Net white space2,400 m2 (E5)
Floor loading12 kPa (E5)
Clear height3.2 m (E5)
Design dry bulb34 degC (E3)
Firm grid capacity14 MVA (E5)
Contracted power12 MW (E5)
Current site peak7.4 MW (E5)
Current IT load4.9 MW (E5)
Busway ampacity400 A (E5)
Tap-off rating63 A (E5)
Plant capacity6,800 kW (E5)
Plant supply / return6 degC (E5) / 12 degC (E5)
Pumped flow available9,000 l/min (E3)

Baseline as supplied. E5 means supplied by the client — a declared rating, contract term or design value as given to us, not measured or surveyed by us. E3 marks a figure that is estimate-grade by nature; E0 marks a library default.

No new or increased connection capacity is available from the DSO in this metro before the 2030s. The existing firm capacity is therefore the asset, and the whole question is how much compute can be produced from it.

5. Electrical capacity analysis

ConstraintTypeRacks permittedBasisRelief
Rack feed / tap-off ratinggate0 racks (E0)platform needs 205 [174–236] A (E0) per rack; installed tap-offs rated 63 A (E5)Higher-rated tap-off units (and busway if ampacity does not allow)
Transformer capacitycapacity8 [4–11] racks (E0)1,330 [845–1,810] kW (E3) usable after redundancy and deratingReplace / add transformer capacity (uprate ~60%)
UPS capacity (protected load)capacity8 [7–8] racks (E0)1,100 kW (E0) of protected-load headroom after N+1 redundancyAdd UPS modules / new UPS block
Busway ampacitycapacity12 [12–13] racks (E0)8 run(s) at 400 A derated to 0.8 -> 1,720 kW (E0)Replace busway with 800-1000 A and new tap-off units
Firm supply (grid import + behind-the-meter)capacity28 [25–30] racks (E0)4,600 kW (E3) of firm-supply headroom at PUE 1.2 [1.15–1.28]Behind-the-meter supply: BESS-2MW-8MWh (bess, 2 MW)

A gate either passes (it does not limit the hall) or fails (it permits no racks until relieved). Rack counts carry the weakest evidence class among the constraints evaluated.

6. Thermal and cooling analysis

ConstraintTypeRacks permittedBasisRelief
Residual air load removal per rackgate0 racks (E0)13.5 [10.6–21.3] kW (E0) of air-side load per rack against 9 kW (E3) the hall can remove per positionAdd in-row cooling or rear-door heat exchangers for the residual air load
Achievable facility water temperaturegate0 racks (E0)TCS target 30 [27–32] degC (E0) needs facility water at or below 25 [21–28] degC (E0); dry coolers at design dry-bulb delivers 44 [42–46] degC (E0)Adiabatic assist plus trim chiller on the high-temperature loop
CDU capacity (derated to site water temperature)capacity22 [15–26] racks (E0)2,700 [2,070–2,970] kW (E0) usable against 122 [112–131] kW (E0) of liquid load per rack; 24 [21–26] degC (E0) approach availableAdd CDU capacity (one further unit per bank)
Hydraulic flow capacitycapacity69 [64–75] racks (E0)9,000 l/min (E3) available against 130 [120–140] l/min (E0) per rack (~1.45 l/min/kW at 10 K delta-T)Uprate pumps and secondary pipework
Chilled-water plant capacitycapacity140 [89–179] racks (E0)1,900 kW (E3) of plant headroom against 13.5 [10.6–21.3] kW (E0) per rack — residual air load only (liquid rejected to a dedicated high-temperature loop)Uprate chilled-water plant (+50%) or add a dedicated high-temperature loop
Cooling architecture per-rack capabilitygatepasses — not limitingfull_dlc is practically capable of 150 [120–160] kW (E0) per rack; the target platform draws 135 [132–142] kW (E0)—

A gate either passes (it does not limit the hall) or fails (it permits no racks until relieved). Rack counts carry the weakest evidence class among the constraints evaluated.

7. Physical constraints

ConstraintTypeRacks permittedBasisRelief
Available rack positionscapacity180 racks (E3)180 of 560 positions available in DH-02De-tenant further positions / release white space
Floor loadinggatepasses — not limiting972 [894–1,050] kg/m2 (E0) imposed against 1,224 kg/m2 (E5) design capacityLoad spreading / remove raised floor and deploy on slab

A gate either passes (it does not limit the hall) or fails (it permits no racks until relieved). Rack counts carry the weakest evidence class among the constraints evaluated.

8. Power and thermal interaction

Power and thermal are not independent budgets. Every kilowatt the cooling architecture consumes is a kilowatt of grid capacity that cannot be sold as compute, so the choice of cooling architecture directly changes the electrical envelope. The table shows the same hall under each architecture.

ScenarioArchitecturePUE usedRacks as foundRacks after ladderBinds firstBinds last
Retained air, grid onlyretained_air1.45 [1.35–1.6] (E0)0 racks (E0)0 racks (E0)Rack feed / tap-off ratingCooling architecture per-rack capability
Rear-door heat exchangers, grid onlyrdhx1.35 [1.28–1.45] (E0)0 racks (E0)0 racks (E0)Rack feed / tap-off ratingCooling architecture per-rack capability
Hybrid DLC on retained plant, grid onlyhybrid_dlc1.3 [1.22–1.4] (E0)0 racks (E0)26 racks (E0)Rack feed / tap-off ratingFirm supply (grid import + behind-the-meter)
Full DLC, grid onlyfull_dlc1.2 [1.15–1.28] (E0)0 racks (E0)28 racks (E0)Rack feed / tap-off ratingFirm supply (grid import + behind-the-meter)
Full DLC plus behind-the-meter supplyfull_dlc1.2 [1.15–1.28] (E0)0 racks (E0)62 racks (E0)Rack feed / tap-off ratingFirm supply (grid import + behind-the-meter)

A better cooling architecture buys compute out of the same grid connection.

9. Economics

ScenarioRacksTotal capexCapex per rack enabledAnnual energy costEnergy cost per GPU-hourCritical pathEconomicsLifecycle cost
Retained air, grid only0 racks (E0)———————
Rear-door heat exchangers, grid only0 racks (E0)———————
Hybrid DLC on retained plant, grid only26 racks (E0)≥ 6,630,000 [3,310,000–13,300,000] EUR (E0)255,000 [127,000–510,000] EUR/rack (E0)4,200,000 [2,480,000–7,470,000] EUR (E0)0.256 [0.151–0.456] EUR/gpu*h (E0)160 [80–210] weeks (E0)NOT decision-grade48,600,000 [28,100,000–88,000,000] EUR (E0)
Full DLC, grid only28 racks (E0)≥ 6,220,000 [3,110,000–12,400,000] EUR (E0)222,000 [111,000–444,000] EUR/rack (E0)4,170,000 [2,510,000–7,360,000] EUR (E0)0.236 [0.142–0.417] EUR/gpu*h (E0)160 [80–210] weeks (E0)NOT decision-grade47,900,000 [28,200,000–86,000,000] EUR (E0)
Full DLC plus behind-the-meter supply62 racks (E0)≥ 18,800,000 [9,420,000–37,700,000] EUR (E0)304,000 [152,000–608,000] EUR/rack (E0)9,240,000 [5,570,000–16,300,000] EUR (E0)0.236 [0.142–0.417] EUR/gpu*h (E0)160 [80–210] weeks (E0)NOT decision-grade111,000,000 [65,100,000–201,000,000] EUR (E0)

Cost basis: Class 5 (order of magnitude): -50% / +100%. Excludes IT hardware, migration and lost tenancy revenue. A total marked with ≥ is a lower bound: a cost it needs has no price. A dash means no rack can be deployed in that architecture and no relief exists, so the figure is undefined rather than zero.

ObjectiveWhat it optimisesArchitecture it selectsRacks
max computeMaximum deployable compute.Full DLC plus behind-the-meter supply62 racks (E0)
min costLowest capital cost per rack enabled.Full DLC, grid only28 racks (E0)
fastestEarliest full energisation.Full DLC plus behind-the-meter supply62 racks (E0)

The same scenarios ranked under each objective. The recommendation above uses the stated objective; where another objective selects a different architecture, that is a judgement for the client, not for the model.

How the recommended capex is builtAmount
Relief works along the headroom ladder (section 2)14,900,000 [7,450,000–29,800,000] EUR (E0)
In-hall conversion of the 62 racks deployed3,410,000 [1,700,000–6,820,000] EUR (E0)
Initial CDU kit — assumed, not installed (3 CDU unit(s) added)540,000 [270,000–1,080,000] EUR (E0)
NOT PRICED — CDU commissioning and flushing (7 x unit; 5 places)no price: excluded
NOT PRICED — CDU hydraulic integration and controls (7 x unit; 5 places)no price: excluded
Total (the headline capex) — LOWER BOUND: the unpriced components above are excluded18,800,000 [9,420,000–37,700,000] EUR (E0)

The ladder's cumulative figure covers the relief works only; the headline adds the per-rack conversion inside the hall and the CDUs the model assumed so the liquid scenarios could be solved (the hall has no CDU schedule on file; those units must be bought).

Recurring cost (recommended architecture)AmountBasis
Grid electricity price used140 [90–220] EUR/MWh (E0)library placeholder, not the site's tariff
Annual site energy66,000 [61,800–74,000] MWh (E0)utilisation x facility load x 8,760 h
Annual energy cost (recurring)9,240,000 [5,570,000–16,300,000] EUR (E0)all energy at the grid price

Operating cost is stated separately from capital. It covers energy and, where on-site generation is installed, that generation's declared operating cost; it excludes the non-energy operating cost of the cooling plant.

Behind-the-meter generation is installed on this path but its operating cost cannot be computed: BESS-2MW-8MWh: annual_run_hours not declared; BESS-2MW-8MWh: no energy cost basis (declare opex_eur_per_MWh, or fuel_price_eur_per_MWh with electrical_efficiency); BESS-2MW-8MWh: variable_om_eur_per_MWh not declared (0 if the fuel route already includes it); BESS-2MW-8MWh: fixed_om_eur_per_kW_year not declared (0 if carried elsewhere). The annual energy cost above therefore prices ALL energy at the grid price, which the hall would not pay. Supply these inputs to replace that figure.
Lifecycle cost over 10 years — LOWER BOUND
111,000,000 [65,100,000–201,000,000] EUR (E0)
Limited by: capex at year 0 plus the annual energy cost for 10 years, undiscounted, flat prices, no escalation; excludes IT hardware, migration, lost tenancy revenue, non-energy operating cost of the cooling plant, and decommissioning
Cost basisLines
library placeholder (not a price)8 lines

What each price in this study rests on. The accuracy class above follows the weakest line, not the average.

8 of 8 priced lines are library placeholders rather than quotations, which is why this estimate is stated at the accuracy class above. Each quotation obtained replaces a placeholder and tightens the whole estimate; the constraint that binds is worth quoting first.
Public retrofit cost benchmarks currently span roughly 2 to 12 MEUR per MW — a four- to sixfold spread. No figure in this section should be treated as a market benchmark; they are screening estimates pending site-specific quotations.

10. Sensitivity

One-at-a-time sensitivity on the recommended architecture, evaluated against the relieved case rather than the hall as found. Inputs are ranked by how far each moves the answer; the ones at the top are the ones worth paying to measure.

Input variedRacksChange vs base case
Contracted power 20% lower48 racks (E0)-14 racks (E0)
PUE 10% worse than assumed57 racks (E0)-5 racks (E0)
Platform rack power 5% higher59 racks (E0)-3 racks (E0)
Contracted power at full firm capacity63 racks (E0)1 racks (E0)
PUE 10% better than assumed63 racks (E0)1 racks (E0)
Per-position air capacity at 20 kW62 racks (E0)0 racks (E0)
Liquid capture fraction 5% lower62 racks (E0)0 racks (E0)

11. Risk register

RiskDescriptionLead time exposure
Achievable facility water temperatureAdiabatic assist reintroduces water consumption; check permits and WUE targets.32 [20–48] weeks (E0)
Transformer capacityLead time, not construction, is usually the schedule driver. Applies to 2 rungs of the ladder.160 [80–210] weeks (E0)
Busway ampacityRequires hall outage or phased de-tenanting. Applies to 5 rungs of the ladder.36 [24–52] weeks (E0)
Firm supply (grid import + behind-the-meter)No combustion consent required; grid-code compliance and fire separation govern the programme.30 [19.5–40.5] weeks (E0)
Firm supply (grid import + behind-the-meter)Emissions consent and fuel supply are the schedule risk, not the equipment.44 [28.6–59.4] weeks (E0)
Firm supply (grid import + behind-the-meter)In most target metros this relief does not exist inside the decision horizon. Behind-the-meter supply is the only lever that moves this constraint.260 [150–520] weeks (E0)
Evidence baseThe dominant inputs in this study are assumed rather than measured. Twelve months of hall trend data would move the headline from an estimate to a reconciled figure.—
StructuralFloor loading is screened, not assessed. A structural engineer must sign off before any deployment.—
HydraulicsPressure drop and pipe sizing are not modelled at screening level; a hydraulic model is required before design.—
TenancyReleasing positions is a commercial and contractual exercise with revenue at risk, not an engineering one.—

12. Recommendation and decision gates

Proceed with Full DLC plus behind-the-meter supply. The same hall with on-site firm supply where the grid connection binds. The only scenario whose capacity is set by what can be built rather than by the queue. On the modelled inputs this unlocks 62 racks of NVIDIA GB300 NVL72 against 0 as found.

13. Scope, basis and limitations

This study is an engineering opinion supported by a documented model. It is not a design package and confers no design liability. The following are outside scope:

Every quantity in this report carries an evidence class; Appendix A lists the assumptions and sources relied upon and the provenance digest of each headline quantity. No number here is a measurement of a physical asset unless it is labelled E5 or above — and E5 means supplied by the client (a declared rating, contract term or design value, or the client's own data as given), not measured or surveyed by us.

EVIDENCE DISCLOSURE: this is a screening study built on library defaults and assumed inputs. electrical capacity is E0 where an issued deliverable requires E3; cooling performance is E0 where an issued deliverable requires E2; capex is E0 where an issued deliverable requires E1. These conclusions are not sufficient to support procurement, construction or an investment committee decision on their own; they are sufficient to decide whether to spend money finding out. The inputs listed in Appendix A.1 are what must be measured to lift them.

14. Model accuracy against instrumented sites

Two different things get called accuracy. The ranges shown throughout this report are input uncertainty propagated through the model — they say how much the answer moves when an input is uncertain. This section is the other one: how far this engine's outputs have been reconciled against data from instrumented sites, which is the only thing that can tell you whether the model itself is right.

Model accuracy against instrumented sites has not been established: 0 reconciled observations across 0 sites, covering 0 of 5 model outputs. Every figure in this report is modelled. The uncertainty ranges shown come from input uncertainty propagated through the model, not from the difference between this engine's predictions and site data — no such difference has been recorded yet.
Model outputStateObservationsSitesMedian biasLast observation
Racks permitted by rack feed tapoffuncalibrated00——
Racks of the target platform actually deployeduncalibrated00——
Deployable IT load in the halluncalibrated00——
Weeks from go-ahead to full capacityuncalibrated00——
Delivered capex for the worksuncalibrated00——

Bias is the median of observed / predicted, so a positive figure means the model has run conservative. An output with no observations is reported as uncalibrated rather than omitted.

Reconciliation is how a figure in this report moves from estimated to field-validated. It requires site data we do not have and cannot generate: interval metering at the relevant point, a BMS trend, or a commissioning record. Where this study recommends instrumentation, that is what it is for — the client gets a better answer next time, and the model gets an observation it can be held to.

Appendix A — Assumptions, provenance and validation status

Every number in this report carries an evidence class. The class of a computed number is never higher than the weakest of its inputs, so a model applied to measured data yields a modelled number and never a measurement.

ClassMeaning
E0assumed
E1modelled
E2simulated
E3estimated
E4validated against test data
E5supplied by the client (not measured or surveyed by us)
E6field-validated
E7observed in operation

E5 means supplied by the client — a declared rating, contract term or design value, or the client's own data as given. It is not a measurement we made, and it has not been verified by a site survey.

A.1 Assumptions relied upon

A.2 Sources

A.3 Provenance of headline quantities

QuantityEvidenceModelDigest
deployable racks as foundE0input2251cf0df6fb
deployable racks after relief measuresE0input90db47981317
deployable IT loadE0envelope.it_loada4e3fd845acb
elapsed weeks to energise the full envelopeE0inputd0aab02069a1
total capexE0economics.total_capex9eed5fbc0658
racks before step 1E0input57e2e78db498
racks after step 1E0input85b2bc621f00
Higher-rated tap-off units (and busway if ampacity does not allow) for 62 racksE0envelope.relief_capex147ba26046e4
tap-off lead timeE0input7a5fc57ce1e4
racks before step 2E0input158e8bfa6770
racks after step 2E0input700ff34e59e2
Add in-row cooling or rear-door heat exchangers for the residual air load for 62 racksE0envelope.relief_capexedd4d4501790
in-row / RDHx lead timeE0inputfe48412ff79a
racks before step 3E0input97d684abc6e0
racks after step 3E0inputd9cc107e9ef0
adiabatic assist and trim chillerE0inputaf0380aad4fa
lead timeE0input3141b684dcc2
cost per kW unlocked at step 3E0input2429f9df92bf
racks before step 4E0inputec6a187a151c
racks after step 4E0inpute5f4587dc18d
transformer and switchgear uprateE0costs.scaled_reliefa9ead11db2b8
power transformer lead timeE0input010015f8a59e
racks before step 5E0inputfee83603c8b2
racks after step 5E0input9fa15f724191
UPS module addition, installedE0costs.scaled_reliefc872f896fe0c
UPS lead timeE0input843c6ad78c29
cost per kW unlocked at step 5E0input829a9d9356bc
racks before step 6E0inputad285ced026e
racks after step 6E0input77feda0334a7
busway and tap-off works, per runE0costs.scaled_relief8bca5c542732
busway and tap-off lead timeE0input74ff17170551
cost per kW unlocked at step 6E0input338dcc79c4e4
racks before step 7E0inputf40dcd6f1aa0
racks after step 7E0inputd1074967c022
additional CDU: supplied and mechanically installedE0costs.scaled_relief053f8a554b8c
CDU lead timeE0input77ae364db11a
cost per kW unlocked at step 7E0input628ad8c40217
racks before step 8E0input3387af96d966
racks after step 8E0inputcb2676ac8d5d
UPS module addition, installedE0costs.scaled_reliefc872f896fe0c
UPS lead timeE0input843c6ad78c29
cost per kW unlocked at step 8E0input8f918f41cfe3
racks before step 9E0input16a2bb6299a8
racks after step 9E0input960dbf5dd25c
BESS-2MW-8MWh installed capexE0power.btm_capex6d5723d85dba
BESS-2MW-8MWh lead timeE0input6b920c9df84d
cost per kW unlocked at step 9E0input1e2d4014ffb6
racks before step 10E0inputde69563717d8
racks after step 10E0inputfbdcf5cb2f3f
busway and tap-off works, per runE0costs.scaled_relief8bca5c542732
busway and tap-off lead timeE0input74ff17170551
cost per kW unlocked at step 10E0input5968e91375ca
racks before step 11E0inputa8109f1916d5
racks after step 11E0input519c3c15d3dd
additional CDU: supplied and mechanically installedE0costs.scaled_relief053f8a554b8c
CDU lead timeE0input77ae364db11a
cost per kW unlocked at step 11E0inputa0505c39fe74
racks before step 12E0input78e4bb9838e6
racks after step 12E0input0c680a5c5b56
GEN-5MW installed capexE0power.btm_capex1be583b10fb5
GEN-5MW lead timeE0input481a422b0494
cost per kW unlocked at step 12E0input1ab1faf58c6a
racks before step 13E0inputa4ddfec8e8bd
racks after step 13E0input2209fe0bf7d0
busway and tap-off works, per runE0costs.scaled_relief8bca5c542732
busway and tap-off lead timeE0input74ff17170551
cost per kW unlocked at step 13E0inputeee5feb9ead9
racks before step 14E0input68af5e73ee6b
racks after step 14E0input165631b4129f
transformer and switchgear uprateE0costs.scaled_reliefa9ead11db2b8
power transformer lead timeE0input010015f8a59e
cost per kW unlocked at step 14E0inputd0dffe923585
racks before step 15E0inputaf265f35b839
racks after step 15E0inpute22ce0c897d7
UPS module addition, installedE0costs.scaled_reliefc872f896fe0c
UPS lead timeE0input843c6ad78c29
cost per kW unlocked at step 15E0input31fa46fb8fba
racks before step 16E0input74a2f3ac10bf
racks after step 16E0inputdf141571107d
additional CDU: supplied and mechanically installedE0costs.scaled_relief053f8a554b8c
CDU lead timeE0input77ae364db11a
cost per kW unlocked at step 16E0inputf67577db3fdd
racks before step 17E0inputfd92b7157817
racks after step 17E0inputb1dbf0553bee
busway and tap-off works, per runE0costs.scaled_relief8bca5c542732
busway and tap-off lead timeE0input74ff17170551
cost per kW unlocked at step 17E0input2be504be40dc
racks before step 18E0input284dc52db335
racks after step 18E0input2634a2d87285
busway and tap-off works, per runE0costs.scaled_relief8bca5c542732
busway and tap-off lead timeE0input74ff17170551
racks before step 19E0input3f9ddadacb88
racks after step 19E0input21b37f3b00d9
additional CDU: supplied and mechanically installedE0costs.scaled_relief053f8a554b8c
CDU lead timeE0input77ae364db11a
cost per kW unlocked at step 19E0inputd9490469db4e
racks before step 20E0input25b83a93faec
racks after step 20E0inputb6813b6b8083
UPS module addition, installedE0costs.scaled_reliefc872f896fe0c
UPS lead timeE0input843c6ad78c29
cost per kW unlocked at step 20E0input32589fd051c3
racks before step 21E0input24f076aba591
racks after step 21E0input083abc3511b5
grid reinforcement lead timeE0input47721a918c66
capex of relief measures taken along the headroom ladderE0economics.relief_capexdee1a6789921
longest relief lead time on the pathE0input505fa5f7a1d4
elapsed at 8 racksE0inputde5547aa0005
racks energised at week 32E0input8af3af83e35b
elapsed at 12 racksE0input383dd97ad586
racks energised at week 160E0input6b7f40267215
elapsed at 22 racksE0inputad779bcadf66
racks energised at week 160E0input6b7f40267215
elapsed at 25 racksE0input9439e9463b2e
racks energised at week 160E0input6b7f40267215
elapsed at 28 racksE0input9665f0a2280d
racks energised at week 160E0input6b7f40267215
elapsed at 31 racksE0input4153e0045c8b
racks energised at week 160E0input6b7f40267215
elapsed at 33 racksE0inpute4f25ae43d0e
racks energised at week 160E0input6b7f40267215
elapsed at 34 racksE0inpute413af818eac
racks energised at week 160E0input6b7f40267215
elapsed at 39 racksE0inputf9cd10496cdc
racks energised at week 160E0input6b7f40267215
elapsed at 40 racksE0input49d2236f51bd
racks energised at week 160E0input6b7f40267215
elapsed at 43 racksE0input24ba0011ed58
racks energised at week 160E0input6b7f40267215
elapsed at 44 racksE0inputcddac00fae3f
racks energised at week 160E0input6b7f40267215
elapsed at 47 racksE0inputed70ce380373
racks energised at week 160E0input6b7f40267215
elapsed at 55 racksE0input70b008bb79b9
racks energised at week 160E0input6b7f40267215
elapsed at 61 racksE0inputae1de8ef84ce
racks energised at week 160E0input6b7f40267215
elapsed at 62 racksE0input624861550c6c
racks energised at week 160E0input6b7f40267215
retained_air: racks after ladderE0inputc9d9dbe18f92
rdhx: racks after ladderE0input10d77c74a6ae
hybrid_dlc: racks after ladderE0inputcc55e0a89bc3
hybrid_dlc: weeks to full capacityE0input6407c94095d9
full_dlc: racks after ladderE0inputbcaf71527669
full_dlc: weeks to full capacityE0input2fe03c190ef9
full_dlc_btm: racks after ladderE0input2d259c82f5e9
full_dlc_btm: weeks to full capacityE0inputf1c9d982adec
installed rack positionsE3input67bea46c790d
positions available for redeploymentE3inputc7ed0c853ebf
hall design density per rackE5inputd8eb3acbba02
hall net white spaceE5inputf3528504b5a3
hall design floor loadingE5inputad256b73d58a
clear heightE5inputcf6bc40ec84a
summer design dry-bulbE3input7312d718f36d
firm connection capacityE5input12bfb67ec92b
contracted capacityE5inputcebe404ab198
current site peak demandE5inputf3099d912f28
current protected IT loadE5input20c4f264d7da
installed busway ampacityE5input0de2f4c2f72e
installed tap-off ratingE5input97fcd8433c84
chilled-water plant capacityE5inputcedbd39b6085
available pumped flowE3input7ebcc1ab3857
Rack feed / tap-off rating: gate failsE0input4aa8886b8226
(transformer headroom available for new IT load / GB300 NVL72 rack TDP) (floored to whole racks)E0constraints.floor_racksedb30cfae0fa
(UPS headroom for new IT load / GB300 NVL72 rack TDP) (floored to whole racks)E0constraints.floor_racksc8e62be34b0a
(total usable busway capacity in hall / GB300 NVL72 rack TDP) (floored to whole racks)E0constraints.floor_racksbf7b469cd3d1
(firm supply headroom available for new IT load / GB300 NVL72 rack TDP) (floored to whole racks)E0constraints.floor_racks0fecb91fef87
Residual air load removal per rack: gate failsE0input26165e87d919
Achievable facility water temperature: gate failsE0input220f8c8a7543
(CDU-ROW-assumed usable capacity at site conditions / gb300_nvl72 liquid load per rack) (floored to whole racks)E0constraints.floor_racks25573ad8fd4c
racks permitted by available pumped flow (floored to whole racks)E0constraints.floor_racksa0c7fccb5cd0
(chilled-water plant headroom / gb300_nvl72 residual air load per rack) (floored to whole racks)E0constraints.floor_racks2a32802480d0
rack positions available in hall (floored to whole racks)E3constraints.floor_racks659e992bdc64
PUE, retained air architectureE0input9f96820c74f4
retained_air: racks as foundE0input8471d3c25f5c
retained_air: racks after ladderE0inputc9d9dbe18f92
PUE, rear-door heat exchanger architectureE0input9cd90386fca6
rdhx: racks as foundE0input77908b548fb2
rdhx: racks after ladderE0input10d77c74a6ae
PUE, hybrid DLC on legacy plantE0input9c10874a8f81
hybrid_dlc: racks as foundE0input1011ee0e8e06
hybrid_dlc: racks after ladderE0inputcc55e0a89bc3
PUE, full DLC with high-temperature loopE0input37e16e4a98d9
full_dlc: racks as foundE0input079192290378
full_dlc: racks after ladderE0inputbcaf71527669
PUE, full DLC with high-temperature loopE0input37e16e4a98d9
full_dlc_btm: racks as foundE0input980324e921db
full_dlc_btm: racks after ladderE0input2d259c82f5e9
retained_air: racks unlockedE0input2e4138fcac55
rdhx: racks unlockedE0inpute9952b43b4be
hybrid_dlc: racks unlockedE0input8eba1a207998
hybrid_dlc: capex per rack enabledE0economics.capex_per_rackc231de706945
annual energy costE0economics.energy_costf35d99e09dad
energy cost per GPU-hourE0economics.energy_per_gpu_hour3e1397117363
hybrid_dlc: critical pathE0inputfd4bb27c96c2
lifecycle cost over 10 yearsE0economics.lifecycle_costc0c7b3b2c957
full_dlc: racks unlockedE0input8887e6b75586
full_dlc: capex per rack enabledE0economics.capex_per_rackb1117dd9e458
annual energy costE0economics.energy_costc6e2b66f7cd7
energy cost per GPU-hourE0economics.energy_per_gpu_hour9f0764431542
full_dlc: critical pathE0inpute150e1d1a44b
lifecycle cost over 10 yearsE0economics.lifecycle_costa7fe3ba3d2a3
full_dlc_btm: racks unlockedE0input7d7b81a69f10
full_dlc_btm: capex per rack enabledE0economics.capex_per_rack9b9420d1d44f
annual energy costE0economics.energy_costc6e2b66f7cd7
energy cost per GPU-hourE0economics.energy_per_gpu_hour9f0764431542
full_dlc_btm: critical pathE0input1bfd8e2425a5
lifecycle cost over 10 yearsE0economics.lifecycle_cost099a6a050f4a
full_dlc_btm: racks under max_computeE0input03622d66b673
full_dlc: racks under min_costE0input4a678bdcfdb2
full_dlc_btm: racks under fastestE0input11903e200727
capex of relief measures taken along the headroom ladderE0economics.relief_capexdee1a6789921
in-hall conversion capexE0economics.conversion_capex31aac42971b6
initial CDU kit (assumed, not installed): supplied and mechanically installedE0costs.scaled_relief457085eb7b50
total capexE0economics.total_capex9eed5fbc0658
all-in electricity priceE0inputee5beeda32eb
annual site energy for the deployed loadE0convert215ce7188587
annual energy costE0economics.energy_costc6e2b66f7cd7
lifecycle cost over 10 yearsE0economics.lifecycle_cost099a6a050f4a
racks under: Contracted power 20% lowerE0input869b37a4a341
delta under: Contracted power 20% lowerE0input65f882b76c13
racks under: PUE 10% worse than assumedE0input43065380960f
delta under: PUE 10% worse than assumedE0input8bd7a84fd489
racks under: Platform rack power 5% higherE0input1c4b952ff282
delta under: Platform rack power 5% higherE0input765a68517e43
racks under: Contracted power at full firm capacityE0input853b07183efd
delta under: Contracted power at full firm capacityE0input9bcc976d41f2
racks under: PUE 10% better than assumedE0input0116a41b8998
delta under: PUE 10% better than assumedE0inputfbe558725f7e
racks under: Per-position air capacity at 20 kWE0input01e03cd90e75
delta under: Per-position air capacity at 20 kWE0inputdd3f45be83c3
racks under: Liquid capture fraction 5% lowerE0input29d531906239
delta under: Liquid capture fraction 5% lowerE0input5626cc77bcc2
lead timeE0input3141b684dcc2
power transformer lead timeE0input010015f8a59e
busway and tap-off lead timeE0input74ff17170551
BESS-2MW-8MWh lead timeE0input6b920c9df84d
GEN-5MW lead timeE0input481a422b0494
grid reinforcement lead timeE0input47721a918c66
Engineering opinion supported by a documented model. Not a design package. Professional indemnity and named-signatory arrangements govern reliance on this report.